-40%

Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A

$ 337.6

Availability: 100 in stock
  • MPN: Acuvim IIR-D-5A-P1
  • Brand: Accuenergy
  • Return shipping will be paid by: Seller
  • Item must be returned within: 30 Days
  • Condition: New
  • All returns accepted: Returns Accepted
  • Refund will be given as: Money back or replacement (buyer's choice)

    Description

    Untitled Document
    Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
    Model:
    Acuvim IIR-D-5A-P1
    | Order No:
    Acuvim-IIR-D-5A-P1
    Revenue grade power meter with data logging capabilites for single and three phase circuits features integrated on-board LCD display, field selectable 5 A or 1 A input for current transformers and wide range AC power supply input.
    Brand:
    Accuenergy
    Model:
    Acuvim IIR-D-5A-P1
    Order No:
    Acuvim-IIR-D-5A-P1
    Condition:
    NEW
    Description
    Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
    Accuenergy Acuvim IIR-D-5A-P1 Offers
    The Accuenergy Acuvim IIR revenue-grade power/energy meter with data logging can be a powerful tool for monitoring the energy consumption of a property, which can provide both accurate billing for tenants while helping identify areas to implement energy efficiency upgrades. This model includes the Acuvim IIR basic unit with field selectable 5A or 1A current input, 100 to 415V AC, 50/60Hz, 100 to 300V DC power supply, and an integrated mounting option with LCD display.
    Functions
    Features
    Revenue grade ANSI C12.20 class 0.2 & IEC 62053-22 class 0.2s
    100ms refresh rate
    Over/Under limit alarms
    Web server and email sending
    Switch status monitoring
    Built-in MODBUS RTU via RS485 port
    Can be upgraded to include Modbus TCP Ethernet, BACnet, Profibus, and a variety of other communication protocols and I/O expansions for added versatility
    Onboard data logging memory is up to 8 MB and each log size is adjustable
    Real time clock allows for any logged events to be accuratelytime stamped
    Included
    Accuenergy Acuvim IIR-D-5A-P1 Revenue Grade Power/Energy Meter, LCD, 5 A/1 A input, 415 Vac/300 Vdc
    Specifications
    Acuvim IIR Specifications
    Accuracy
    Acuvim-II
    Accuracy
    Acuvim-IIR/IIE/IIW
    Resolution
    Range
    Voltage
    0.2%
    0.2%
    0.1V
    20V~1000kV
    Current
    0.2%
    0.2%
    0.1mA
    5mA~50000A
    Power
    0.5%
    0.2%
    1W
    -9999MW~9999MW
    Reactive Power
    0.5%
    0.2%
    1var
    9999Mvar~9999Mvar
    Apparent Power
    0.5%
    0.2%
    1VA
    0~9999MVA
    Power Demand
    0.5%
    0.2%
    1W
    -9999MW~9999MW
    Reactive Power Demand
    0.5%
    0.2%
    1var
    -9999Mvar~9999Mvar
    Apparent Power Demand
    0.5%
    0.2%
    0.2%
    0~9999MVA
    Power Factor
    0.5%
    0.2%
    0.001
    -1.000~1.000
    Frequency
    0.2%
    0.2%
    0.01Hz
    45.00~65.00Hz
    Energy Primary
    0.5%
    0.2%
    0.1kWh
    0-99999999.9kWh
    Energy Secondary
    0.5%
    0.2%
    0.001kWh
    0-999999.999kWh
    Reactive Energy Primary
    0.5%
    0.2%
    0.1kvarh
    0-99999999.9kvarh
    Reactive Energy Secondary
    0.5%
    0.2%
    0.001kvarh
    0-999999.999kvarh
    Apparent Energy Primary
    0.5%
    0.2%
    0.1kVAh
    0-99999999.9kVAh
    Apparent Energy Secondary
    0.5%
    0.2%
    0.001kVAh
    0-999999.999kVAh
    Harmonics
    1.0%
    1.0%
    0.1%
    0.0%~100.0%
    20.0%~100.0% (IIR/IIE/IIW)
    Phase Angle
    2.0%
    2.0%
    0.1°
    0.0°~359.9°
    Unbalance Factor
    2.0%
    2.0%
    0.1%
    0.0%~100.0%
    Running Time
    0.01h
    0~9999999.99h
    Current Inputs (Each Channel)
    Nominal Current
    5A /1A
    Metering Range
    0~10A AC
    Withstand
    20Arms continuous,
    100Arms for 1 second, non-recurring
    Burden
    0.05VA (typical) @ 5Arms
    Pickup Current
    0.1% of nominal
    Accuracy
    0.2% full scale
    Voltage Inputs (Each Channel)
    Nominal Full Scale
    400V AC L-N, 690V AC L-L (+20%)
    Withstand
    1500V AC continuous
    2500V AC, 50/60Hz for 1 minute
    Input Impedance
    2Mohm per phase
    Metering Frequency
    45Hz~65Hz
    Pickup Voltage
    10V AC (30V AC for Acuvim IIR/IIE/IIW)
    Accuracy
    0.2% full scale
    Energy Accuracy (Acuvim IIR/IIE/IIW)
    Active
    According to IEC 62053-22: Class 0.2s
    According to ANSI C12.20: Class 0.2s
    Reactive (according to IEC 62053-23)
    Class 2
    Harmonic Resolution
    Metered Value
    Acuvim II: 31st harmonic
    Acuvim IIR/IIE/IIW: 63rd harmonic
    Control Power
    Universal
    AC or DC
    Operating Range
    100~415V AC, 50/60Hz
    100~300V DC
    Burden
    5W
    Frequency
    50/60Hz
    Withstand
    3250V AC, 50/60Hz for 1 minute
    Installation Category III (Distribution)
    Low Voltage DC Control Power (Optional)
    Operating Range
    20~60V DC
    Burden
    5W
    Communication
    Rs-485 (standard)
    MODBUS® RTU Protocol, 2-wire connection
    1200~38400 baud rate
    The second Rs-485 Port (Optional)
    MODBUS® RTU Protocol, 2-wire connection
    4800~38400 baud rate
    Ethernet (Optional)
    10M/100M BaseT
    MODBUS® TCP/IP Protocol
    Data Browsing through HTTP
    Sending e-mail automatically
    PROFI-BUs (Optional)
    PROFIBUS-DP/V0 Protoco
    Work as PROFIBUS slave, baud rate adaptive, up to 12M
    Typical input bytes: 32, typical output bytes: 32
    PROFIBUS standard according to EN 50170 vol.2
    Terms & Conditions
    Item Condition:
    Unless specified otherwise all products listed are Brand New in the original factory packaging and include a full factory warranty.
    Shipping:
    We currently only ship to U.S. buyers. We ship items within one or two business days from payment. We do not process shipments on weekends and holidays. Local pick up is not available. We only ship to addresses verifiable by either PayPal or credit card issuing bank.
    Please note that we cannot alter the address once a purchase is made. In the case of PayPal payment, we will ship orders when the payment is marked “Eligible” for PayPal Seller’s protection.
    *Shipping Rates are for Continental US, Please Contact us for other US Destinations
    Payment:
    Currently all payments must be made directly though PayPal
    Sales Tax:
    We are required to charge sales tax in North Carolina
    Return Policy:
    If for any reason you are not 100% satisfied with a product you receive from us, you may return the regular stock product within 30 days from the time of receipt, for a full refund or exchange of the product you purchased (less any shipping costs). Within this time, products may be returned; freight prepaid and must be in their original packaging and in resalable condition.
    Shipping errors, missing items or damages must be reported to us immediately (damages should be accompanied by a signed bill of lading acknowledging the damage). Items returned will be inspected for damage or misuse at which time they may be subject to restocking fees, other fees or refused, prior to the issuance of any credit.